Can be replaced with AVT.
AVT series air velocity transmitters are engineered for building
automation in the HVAC/R industry. The AVT measures air velocity and
temperature, with field selectable range and output options in a
single device. Designed with a duct mount probe and adjustable
collar suitable for round or rectangular ducts.
AVT series devices include:
• 3 field selectable measurement ranges for air velocity, selectable via jumper.
• Separate readings and outputs for air velocity and temperature.
• Proportional output options include: voltage (0–10 V) and current (4–20 mA).
AVT series device options offer:
• Display
• Field adjustable relay
Accuracy: | < 0.2 m/s + 5 % (Range 0...2 m/s) < 0.5 m/s + 5 % (Range 0...10 m/s) < 1.0 m/s + 5 % (Range 0...20 m/s) |
Measuring units: | m/s, °C |
Supply voltage: | 24 VDC ±10 % / 24 VAC ±10 % |
Power consumption: | 35 mA (50 mA with relay) + 40 mA with mA-outputs |
Output signal 1: | 0...10 V or 4...20 mA (linear to °C) |
Output signal 2: | 0...10 V or 4...20 mA (linear to m/s) |
Optional relay output: | Potential free SPDT 250 VAC, 6 A / 30 VDC, 6 A with adjustable switching point and hysteresis |
Operating temperature: | 0...+50 °C |
Probe: | Adjustable immersion length 50...180 mm, mounting flange included |
Protection standard: | IP54 |
Example
AVT-D-R
Product series
Display
Rele