DPT-Ctrl

DPT-Ctrl is a multifunctional PID controller with differential pressure or air flow transmitter.

DPT-Ctrl enables to control constant pressure or flow of fans, VAV systems or dampers. Its two lined display shows the direction of the control output and the measurement value at the same time. It is possible to select either current or voltage for both the control output and the differential pressure or flow output. The optional autozero function eliminates the need for periodic manual zero point calibration.

 

Technical details

Accuracy (from applied pressure):
(model 2500)
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure):
(model 7000)
Pressure < 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Control signal: 0…10 VDC
Output signal for pressure or air flow (selectable via menu): 0…10 VDC
4…20 mA
PID-parameters: Adjustable via menu
Zero point calibration: Automatic with autozero element (-AZ) or by pushbutton
Supply voltage: 24 VDC ±10 % / 24 VAC ±10 %
Power consumption: < 1.0 W
Operating temperature: -20…+50 °C (with autozero calibration -5...+50 °C)
-40...+50 °C (-40C model)
Protection standard: IP54

DPT-Ctrl

Example
DPT-Ctrl-2500-AZ-D

Model

Product series

DPT-Ctrl
Pressure and flow controller
DPT-Ctrl

Measuring ranges (Pa)

-2500
0...2500
-7000
0...7000
-2500

Zero point calibration

-AZ
With autozero calibration
Standard with pushbutton manual zero point calibration
-AZ

Display

-D
With display
-D

Cold resistance

-40C
40 °C cold resistant (not available with autozero calibration)
Without -40 ºC cold resistance

Other Pressure and flow controllers: