The PS series mechanical differential pressure switches offer a cost effective solution for filter, fan and duct pressure monitoring in building automation systems in the HVAC/R industry. PS series products offer field selectable switching point adjustment.
Accuracy of switching point (low limit typ.): | ±8 Pa (PS1500: ±20 Pa, PS4500: ±100 Pa) |
Accuracy of switching point (high limit max.): | ±15 % |
Service life: | over 1 000 000 switching operations |
Electrical rating (resistive load): | 3 A / 250 VAC (PS200: 0.1 A / 250 VAC) |
Electrical rating (inductive load): | 2 A / 250 VAC (PS200: --) |
Operating temperature: | -20...+60 °C |
Protection standard: | IP54 |