CDT series air quality transmitters are engineered for building automation systems in the HVAC/R industry. The CDT series measures carbon dioxide (CO2) utilizing the industry standard NDIR measurement principle, and temperature (T). Optional relative humidity (rH) measurement is also available in the same device. CDT series devices are available with large touchscreen display making configuration of the device quick and easy. Configuration is also possible via Modbus network.
The CDT-MOD-2000 series transmitters calibrate themselves automatically using ABC logicTM. The ABC logicTM requires that the space in which the transmitter is used needs to to be unoccupied for four hours per day so that the indoor CO2 concentration drops to the outside level. CDT-MOD-2000-DC is a dual channel model with a measuring channel and a reference channel that makes a continuous comparison and the necessary adjustment accordingly. CDT-MOD-2000-DC is also suitable for buildings that are continuously occupied.
CDT-MOD-2000 series devices include:
• Separate field configurable Modbus output for each measurement parameter (CO2, rH, T)
• Offset feature enabling field calibration for each measurement parameter (CO2, rH, T)
• One analog output for selected measurement: voltage (0/2–10 V) or current (4–20 mA)
• 2″ x 3″ touchscreen display
• Time extension button that enables boosting ventilation manually using the touchscreen display
• Optional relay output
Communication: | RS-485 Modbus (RTU) |
Accuracy: | CO2: ±40 ppm + 3 % of reading, DC model: 75 ppm or 10 % of reading (whichever is greater) Temperature: <0.5 °C Relative humidity: ±2…3 % rH at 0…50 °C and 10…90 % rH Total error band includes accuracy, hysteresis and temperature effect over 5...50 °C and 10–90 % rH |
Measuring elements: | Temperature sensor: Pt1000 / Integrated (models with rH-measurement), Non Dispersive Infrared (NDIR) CO2 sensor, thermoset polymer capacitive sensing element for humidity |
Measuring units: | ppm, °C, % rH |
Calibration: | Automatic self-calibration, ABC LogicTM or continuous comparison (DC) |
Supply voltage: | 24 VDC/VAC ±10 % |
Current consumption: | max 90 mA (at 24 V) + 10 mA for each voltage output or 20 mA for each current output |
Output signal for selected measurement: | 0/2…10 V (linear to CO2, rH or T) (2–10 VDC display models only) or 4…20 mA (linear to CO2, rH or T) |
Optional relay output: | Potential free SPDT 250 VAC, 6 A / 30 VDC, 6 A with adjustable switching point and hysteresis |
Operating temperature: | 0...50°C |
Protection standard: | IP20 |
Example
CDT-MOD-2000-1R-D
Product series
Calibration
Mounting
Relay
Relative humidity sensor
Display