DPT-Dual series differential pressure transmitters are engineered for building automation in the HVAC/R industry. DPT-Dual is a technologically advanced transmitter measuring static and differential pressure from two different points, with field selectable units, range and output, all in a single device.
DPT-Dual series devices include:
• Multiple measurement units, field selectable via jumper, including: inWC, mmWC, Pa, mbar.
• 8 field selectable measurement ranges, unidirectional or bi-directional, selectable via jumper.
Accuracy (from applied pressure): (model 2500) |
Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa |
Accuracy (from applied pressure): (model 7000) |
Pressure < 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa |
Zero point calibration: | by pushbutton |
Measuring units: | Pa, kPa, mbar, inchWC, mmWC |
Supply voltage: | 24 VDC ±10% / 24 VAC ±10% |
Power consumption: | < 1.0 W |
Output signals (3-wire): | 2 x 0...10 VDC or 2 x 0...5 VDC (selectable by jumper) |
Operating temperature: | -20...+50 °C |
Response time: | 0.8 / 4 s |
Protection standard: | IP54 |
Example
DPT-Dual-2500-D
Product series
Model type
Measuring ranges (Pa)
Display