DPT-Dual-MOD combines two differential pressure transmitters into one device. It offers a possibility to measure pressure from two different points. It has a Modbus interface and an Input terminal. When using the Input terminal, temperature transmitters can be replaced with temperature sensors. As a result you will save in costs of the devices and in the installation costs.
DPT-Dual-MOD series devices include:
• Multiple measurement units, field selectable via menu, including: Pa, mbar, inchWC, mmWC and psi.
• Input terminal enabling reading of multiple other signals such as temperature or control relays over Modbus
Communication: | RS-485 Modbus (RTU) |
Accuracy (from applied pressure): (model 2500) |
Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa |
Accuracy (from applied pressure): (model 7000) |
Pressure < 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa |
Zero point calibration: | via Modbus or by pushbutton |
Measuring units: | Pa, kPa, mbar, inchWC, mmWC, psi |
Supply voltage: | 24 VDC ±10 % / 24 VAC ±10 % |
Power consumption: | < 1.3 W |
Operating temperature: | -20…+50 °C |
Response time: | 1...20 s selectable via menu |
Protection standard: | IP54 |
Example
DPT-Dual-MOD-2500-D
Product series
Model type
Measuring ranges (Pa)
Display