DPT-MOD

Multifunctional differential pressure transmitters with air flow measurement and Modbus communication

DPT-MOD is a multifunctional transmitter for measuring volume flow, velocity, and static and differential pressure. The measurements can be read and the configuration done via Modbus communication. DPT-MOD requires less wiring than the traditional 3-wire transmitters because multiple devices can be connected on serial line. DPT-MOD can also be used with several different measurement probes such as FloXact™ or pitot tube, and air dampers.

 

DPT-MOD series devices include:
• Two selectable functions:
o Measure and monitor in-duct volume flow, velocity or
differential pressure
o Measure and monitor air flow across centrifugal fans

 

• Multiple selectable measurement units:
o Volume flow: m3/s, m3/h, cfm, l/s
o Velocity: m/s, ft/min
o Pressure: Pa, inWC, mmWC, kPa, mbar

 

• Modbus communication protocol

 

DPT-MOD series device options offer:
• AZ (autozero) function for automatic zero point calibration, eliminating the need for periodic manual autozeroing to ensure long term accuracy

 

 

Technical details

Communication: RS-485 Modbus (RTU)
Accuracy (from applied pressure):
(model 2500)
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure):
(model 7000)
Pressure < 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: automatic with autozero element (-AZ), by pushbutton or via Modbus
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
Flow: m3/s, m3/hr, cfm, l/s, m/s, ft/min
Measuring element: MEMS, no flow-through
Supply voltage: 24 VAC ±10 % / 24 VDC ±10 %
Power consumption: < 1.3 W
-40 °C model: <4.3 W when <0 °C
Output signal: via Modbus
Response time: 1.0−20 s, selectable via menu or via Modbus
Operating temperature: -20…+50 °C (with autozero calibration -5...+50 °C)
-40…+50 °C (-40C model)
Protection standard: IP54

DPT-MOD

Example
DPT-MOD-2500-AZ-D

Model

Product series

DPT
Differential pressure transmitter
DPT

Model type

-MOD
Modbus communication
-MOD

Measuring ranges (Pa)

-2500
-250...2500
-7000
-700...7000
-2500

Zero point calibration

-AZ
With autozero calibration
Standard with pushbutton manual zero point calibration
-AZ

Display

-D
Display
-D

Cold resistance

Without cold resistance
-40C
-40 °C cold resistant (not available with autozero calibration)