The DPI series electronic pressure measuring devices are engineered for building automation in HVAC/R industry. The most technologically advanced and versatile electronic differential pressure switches on the market, combining up to two relay outputs and 0–10 V output options.
The DPI includes the following field selectable features:
• Configurable switching point: Open on rise or fall in pressure
• Hysteresis of setpoint
• Measurement units (Pa, kPa, mmWC, inWC, mbar)
• Measurement range (4 ranges per model)
• Output signal (0−10 V, NO/NC)
• Span and zero point calibration
Accuracy (from FS): | ±1.5 % (±0.7 % with span point calibration) (including: general accuracy, temperature drift, linearity, hysteresis, and repetition error) |
Long term stability, typical 1 year: | ±1 Pa (±8 Pa without autozero element -AZ) |
Zero point calibration: | automatic with autozero element (-AZ) or by pushbutton |
Supply voltage: | 21–35 VDC / 24 VAC ±10 % (without -AZ option) 24 VDC ±10 % / 24 VAC ±10 % (with -AZ option) |
Current consumption: | 35 mA + relays (7 mA each) + AZ (20 mA) + 0…10 V output (10 mA) |
Output signals: | 0…10 V Relay output 1 (250 VAC / 30 VDC / 6 A) Optional relay output 2 (250 VAC / 30 VDC / 6 A) |
Operating temperature: | -10...+50 °C (with autozero calibration -5...+50 °C) |
Response time: | 0.5...10 s |
Protection standard: | IP54 |
Example
DPI±500-2R-D
Product series
Measuring ranges (Pa)
Number of relays
Zero point calibration
Display