DPT-R8 series differential pressure transmitters are engineered for building automation in the HVAC/R industry. The most technologically advanced transmitters on the market measuring static and differential pressure, with field selectable units, range and output, all in a single device.
DPT-R8 series devices include:
• Multiple measurement units, field selectable via jumper, including: inWC, mmWC, Pa, mbar.
• 8 field selectable measurement ranges, unidirectional or bi-directional, selectable via jumper.
• Proportional output options including: voltage (0–10 V / 2-10 V) and current (4–20 mA).
DPT-R8 series device options offer:
• AZ (autozero) function for automatic zero point calibration, eliminating the need for periodic manual autozeroing to ensure long term accuracy
• Backlit display
• Field adjustable span point calibration (i.e. gain)
Accuracy (from applied pressure): (models 250 and 2500) |
Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa |
Accuracy (from applied pressure): (model 7000) |
Pressure< 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa |
Zero point calibration: | automatic with autozero element (-AZ) or by pushbutton |
Measuring units: | Pa, kPa, mbar, inchWC, mmWC, psi |
Measuring element: | MEMS, no flow-through |
Supply voltage: | 24 VDC ±10 % / 24 VAC ±10 % |
Power consumption: | < 1.0 W (< 1.2 W with output current 20 mA) |
Output signals (3-wire): | 0/2…10 VDC 4…20 mA |
Operating temperature: | -20…50 °C (with autozero calibration -5...50 °C) -40…50 °C (-40C model) |
Response time: | 0.8 / 8 s |
Protection standard: | IP54 |
Example
DPT2500-R8-AZ-D
Product series
Measuring ranges
Model type
Zero point calibration
Display
Span point calibration
Cold resistance